- For supplies with Generation systems (including those of Self-consumption of any kind), Storage or Recharge of vehicles according to diagrams 1a, 1b, 1c, 3a, 3b or 4a of the ITC-BT-52 that require several main or secondary three-phase meters of direct measurement (P ≤ 50 kW).
- Modular columns mounted in double insulated boxes.
- Copper plates 20x4 mm (20x4 mm double in phases for columns of 400 A) in general busbar and protection.
- Transparent protective veil with possibility of sealing in the functional fuse protection unit.
- UTE safety fuse bases 22x58 type FS-100.
- Connected with cable H07Z1-R of 16 mm² for counters and 2.5mm² for red wire of the control circuit.
- Space to install a three-phase PLC filter, and / or equipment associated with load management or wave quality (from SPL or other systems), in each supply.
- Switch of Individual Maneuver and cut in load of 4x80 A in each supply.
- Output terminals for cable connection up to 16 mm².
- Terminals for connection of the "Control or Communication Wire" (Red) of 2.5 mm².
- Possibility of coupling a General Maneuvering Column (IGM) of 160A, 250A and 400A load cut: type IGM-MLG (with possible measure of the general line) for the schemes based on collective recharge circuits (1a, 1b and 1c) and type IGM-PST (with overvoltage protector) for the schemes based on individual recharging circuits (3a, 3b and 4a).
* IGM-BSC: Exclusive use in those Centralizations that DO NOT require protection against transient overvoltages: they are powered by an entirely underground network, installed on farms more than 50 meters from any lightning conductor, located in provinces with less than 20 days of storm year according to Map A of the ITC-BT-23 Guide and in which no supply meets any of the situations or risks indicated in Tables A and B of the ITC-BT-23 Guide.