CPM with door (with triple-action latch and lock operated from handle with bolt for padlock) and canopy (with ventilation and anti-mosquito grid) for installation directly on the outside (recessed, semi-recessed or on base) accessible directly from the ground. Entrance of all drivers by diaphanous space in the lower part.
- Single Phase or Three Phase connection with Neutral sectioning and protection by BUCs Size "00".
- Connection point for Neutral Earthing (Maximum admissible section 50 mm2).
- Maximum admissible section of connection cables 120mm2 and 240mm2.
- Transient overvoltage protector PST 1 + 2-12,5 / 25kA and ground protection plate for the farm.
- Triangle for meter mounting (single phase) and space for PLC (three phase) or Modem filter.
- Switch of Single Maneuver 80 A.
- Output terminals for individual phase, neutral and earth bypass of 16 mm2 and signal terminal of 2.5 mm2, with output from their conductors from the bottom.