- CGP for installation inside a building niche or building with a door accessible directly from the ground, fed from the underground network or possibly from the air network (if facade or enclosure
- Possibility of "Network Distribution" (Network Input and Output) and "T" Connection "Dedicated" Connection from the Transformation Center (CGP 630 A).
- Power 1 LGA with output from its drivers from the bottom or top.
- Three-phase supply with Neutral isolation and protection by BUCs: Size "3" for connections up to 630 A. (250 < P ≤ 400 kW)
- Sealable transparent lid.
- Cuba with individual cable glands for each driver (in removable plate on the lower part of the cover).
- Connection point for Neutral Earthing (Maximum admissible section 50 mm2).
- Maximum permissible cable cross section (Connection and LGA): 240 mm2 (Connection in M10 screws).