CGPS TYPE "EXTERIOR CABINET" (AE) FOR FARMS WITH 1 LGA (WITH FOURTH OR CUSTOMER CABINET)
DESCRIPTION
- CGP with door and roof for installation directly on the outside (recessed, semi-recessed or on base) accessible directly from the ground, fed from the underground network or possibly from the Air network (if facade or enclosure
TECHNICAL DATA
- Possibility of "Network Distribution" (Network Input and Output) and "T" Connection CGPs 400 A- Power 1 LGA with output from its drivers from the bottom.
- Three-phase supply with Neutral isolation and protection by BUCs: Size "2" for connections up to 400 A. (100 < P ≤ 250 kW)
- Door with retainer and triple action closure operated from handle with bolt for padlock.
- Tejadillo resistant flashing with ventilation and anti-mosquito grid.
- Entrance of all drivers through open space in the lower part.
- Connection point for Neutral Earthing (Maximum admissible section 50 mm2).
- Sección máxima admisible de cables (Acometida y LGA): 240 mm2 (Conexión en tornillos M10).