- Priority use in Counter Centralizations with measurement columns of any type (CMM-SGC, CMT-SGC, CMM-GAR, CMT-GAR, CMM-DR2 and CMT-DR2), and especially in those that supply facilities for recharging according to the schemes of the ITC-BT-52 based on individual recharging circuits (Schemes 2, 3a, 3b and 4a).
- Intensities of the 4-pole load cut switch with advanced neutral of the IGM: 160A, 250 A and 400 A *.
- Transient Surge Protector Type 1 + 2 of 25 / 100kA.
- Bases BUC-00 with NH-00 125 A fuses in surge discharge circuit.
* IGM 400 A: Exceptional use in centralizations made up of several measuring columns whose horizontal busbars are dimensionedfor a maximum intensity of 400 A.